S8AS-24006N
Product description
[Capacity] 240 W
[Input voltage] 100 to 240 VAC
[Output voltage] 24 V
[Max. cutoff output current (per branch)] 3.8A
[Total output current] 10A
[Number of output branches] 6 branch outputs
[communications functions] None
[Parameter setting] Not changeable
[Withstand voltage] 3.0 kVAC for 1 min between all input terminals collectively and all branch output, all I/O signal, and all communications terminals collectively (Detection current: 20 mA)
2.0 kVAC for 1 min between all inputs and protective earth (Detection current: 20 mA)
1.0 kVAC for 1 min between protective earth and all branch output, all I/O signal, and all communications terminals collectively (Detection current: 20 mA)
500 VAC for 1 min between all branch output and all I/O signal/communications terminals collectively (Detection current: 20 mA)
500 VAC for 1 min between all I/O signal terminals collectively and communications terminals collectively (Detection current: 20 mA)
500 VAC for 1 min between all I/O signal terminals collectively and all output signal terminals collectively (detection current: 20 mA)
[Insulation resistance] 100 M Ohm min. at 500 VDC between the protective earth terminal or all input terminals collectively and all branch output, all I/O signal, and all communications terminals collectively
[Output indicator] Provided (Color: green)
[Conducted EMI] Conforms to EN 61204-3 Class A and FCC Class A.
[Radiated EMI] Conforms to EN 61204-3 Class A.
[Safety standards] cULus: UL508 (Listing. Class2: Per UL1310), CSA C22.2 No.107.1 (Class2: Per CSA C22.2 No.223) cURus: UL60950-1, CSA C22.2 No.60950-1 EN: EN50178, EN60950-1 VDE: VDE0160, VDE0805 Teil1
[SEMI standard] SEMI F47-0706 (200 VAC input)
[Weight] 1,600 g max.